4. SSCNET COMMUNICATION DRIVERS
To next page
(7) Adjusting the CH. 0 transient driver
Adjust this driver as in the adjustment of the fast refresh driver.
1) As in the adjustment of the fast refresh driver,
choose Properties from the My Computer icon to
show the "System Properties" window.
Click [Device Manager].
Choose and double-click "Other devices".
Choose "SNETP DRIVER (Transient CH. 0)" and
click [Properties].
2) The "SNETP DRIVER (Transient CH. 0)" Properties"
window appears.
Click [Resources].
Choose "Memory range" to highlight it and click
[Change Setting...].
3) The "Memory Range" window appears.
Type "D0000-D0FFF" in the Value field and click
[OK].
*Set the same "Memory range" value as set in the
fast refresh driver.
*Section 4.4 (12) provides the SSCNET
Communication Driver Setup Memory Base
Address and driver memory range setting table.
Use it for your reference.
4 − 23