6 ACTUAL VALUES
The relay uses three phase power quantities to determine total energy consumption. All energy quantities can
be reset to zero with the
. Energy cost is also calculated based on the average billing rate programmed in the setpoint
DATA
SETUP \ POWER SYSTEM \ COST OF ENERGY
provide approximate costs. Energy quantities auto-range to show units appropriate to the nominal power.
NOTE: The 750/760 is not a revenue class meter and cannot be used for billing purposes.

ENERGY

[ENTER] for more
POSITIVE WATTHOURS:
0.0 MWh
POSTIVE WATTHOUR
COST: $
NEGATIVE WATTHOURS:
0.0 MWh
NEGATIVE WATTHOUR
COST: $
POSTIVE WATTHOUR
COST: $
POSITIVE VARHOURS:
0.0 Mvarh
NEGATIVE VARHOURS:
0.0 Mvarh
ENERGY USE DATA LAST
RESET: Mar 16 1997
GE Power Management
Courtesy of NationalSwitchgear.com
command found in setpoint heading
CLEAR ENERGY USE DATA?
. Although billing rate structures are usually more complex, these values
The Energy actual values path is:
\ ACTUAL VALUES \ A2 METERING \ ENERGY
This message displays the positive watthours. Real power in the positive direc-
tion will add to this accumulated value. Real power opposite to this direction
will add to the
NEGATIVE WATTHOURS
This message displays the approximate cost of the positive watthours.
0
This message displays the negative watthours. Real power in the negative
direction will add to this accumulated value. Real power opposite to this direc-
tion will add to the
POSITIVE WATTHOURS
This message displays the positive watthours. Real power in the positive direc-
tion will add to this accumulated value. Real power opposite to this direction
0
will add to the
NEGATIVE WATTHOURS
This message displays the approximate cost of the negative watthours.
0
This message displays the positive varhours. Reactive power in the positive
direction will add to this accumulated value. Reactive power opposite to this
direction will add to the
This message displays the negative varhours. Reactive power in the negative
direction will add to this accumulated value. Reactive power opposite to this
direction will add to the
This message displays the last date the energy use data was cleared.
750/760 Feeder Management Relay
value.
value.
value.
value.
NEGATIVE VARHOURS
value.
POSITIVE VARHOURS
6.3 A2 METERING
6.3.7 ENERGY
S1 RELAY SETUP \ CLEAR