10.9 AUTORECLOSE FUNCTIONS (760 ONLY)

10.9 AUTORECLOSE FUNCTIONS (760 ONLY)
The following logic input functions are used in the autoreclose scheme. Refer to Section 14.8: AUTORE-
CLOSE (760 ONLY) on page 14–30 for more detail.
RECLOSE FUNCTIONS
[ENTER] for more
INITIATE RECLOSURE:
Disabled
CANCEL RECLOSURE:
Disabled
BLOCK RECLOSURE:
Disabled
10
10-
12
Courtesy of NationalSwitchgear.com
The Autoreclose Functions setpoints path is:
\ SETPOINTS \ S3 LOGIC INPUTS \ RECLOSE FUNCTIONS
Range: Disabled, Input 1, Input 2, ..., Input 20
Initiates an autoreclose sequence leading to an operation of the 2 CLOSE
relay. This input will NOT cause the 1 TRIP output relay of the 760 to operate.
It is intended for use where the initiating device sends an independent trip to
the breaker at the same time it sends an initiate reclosure to the 760.
Range: Disabled, Input 1, Input 2, ..., Input 20
Cancels a reclosure sequence in progress and blocks the autoreclose scheme
from operating.
Range: Disabled, Input 1, Input 2, ..., Input 20
Cancels a reclosure sequence in progress and blocks the autoreclose scheme
from operating.
750/760 Feeder Management Relay
10 S3 LOGIC INPUTS

10.9.1 DESCRIPTION

10.9.2 SETTINGS