6 ACTUAL VALUES
AUTORECLOSE
[ENTER] for more
AUTORECLOSE SHOT
NUMBER IN EFFECT: 0
AUTORECLOSE SHOTS
REMAINING
AUTORECLOSE SHOT
RATE: 0 /hr
AUTORECLOSE SHOT
COUNT: 0
AR SHOT COUNT LAST
RESET: Oct 25 1998
GE Power Management
Courtesy of NationalSwitchgear.com
The Autoreclose actual values path is:
\ ACTUAL VALUES \ A1 STATUS \ AUTORECLOSE
The present shot number which the autoreclose scheme is using to control
protection settings is displayed in this message. If the scheme has reached
Lockout, the display is the shot number after which a trip caused lockout.
This message displays the number of reclose shots that can still be performed.
After this point, the reclose system will be either reset or locked-out. The value
displayed in this message is the value contained in the Shot Limit memory.
Each time a reclose shot is performed, in a given sequence, this Shot Limit is
reduced by one. The Shot Limit can also be reduced to any given value less
than the programmed value by the current supervision function.
The number of reclosures in the past hour. This value will be cleared by a
command via the front panel or communications.
RESET AR RATE DATA
The total number of reclosures since the
This message displays the last date the Autoreclose counter data was cleared.
If the date has never been programmed, this message will display "Unavail-
able."
750/760 Feeder Management Relay
6.2 A1 STATUS

6.2.7 AUTORECLOSE (760 ONLY)

AR SHOT COUNT LAST RESET
date.