15 S8 TESTING
15 S8 TESTING 15.1 OUTPUT RELAYS
For testing purposes, the relay provides the ability to override the normal function of the solid state and output
contacts. This is done by forcing each to energize or de-energize.
OUTPUT RELAYS
[ENTER] for more
FORCE OUTPUT RELAYS
FUNCTION: Disabled
FORCE 1 TRIP
RELAY: De-energized
FORCE 2 CLOSE
RELAY: De-energized
FORCE 3 AUXILIARY
RELAY: De-energized
FORCE 4 AUXILIARY
RELAY: De-energized
FORCE 5 AUXILIARY
RELAY: De-energized
FORCE 6 AUXILIARY
RELAY: De-energized
FORCE 7 AUXILIARY
RELAY: De-energized
FORCE 8 SELF-TEST
RELAY: De-energized
FORCE SOLID STATE
OUTPUT: De-energized
GE Power Management
Courtesy of NationalSwitchgear.com
The
setpoints path is:
OUTPUT RELAYS
\ SETPOINTS \ S8 TESTING \ OUTPUT RELAYS
Range: Enabled, Disabled
Select Enabled to override the normal operation of the solid state and output
contacts, with the state programmed in the messages that follow. Note that this
setpoint will always be defaulted to the Disabled state at power up.
Range: Energized, De-energized
Select De-energized to force the 1 TRIP relay to the de-energized state while
the setpoint
FORCE OUTPUT RELAYS FUNCTION
gized to force the 1 TRIP relay to the energized state while the setpoint
is set to Enabled .
OUTPUT RELAYS FUNCTION
Range: Energized, De-energized
Force the 2 CLOSE relay state as per the 1 TRIP relay.
Range: Energized, De-energized
Force the 3 AUXILIARY relay state as per the 1 TRIP relay.
Range: Energized, De-energized
Force the 4 AUXILIARY relay state as per the 1 TRIP relay.
Range: Energized, De-energized
Force the 5 AUXILIARY relay state as per the 1 TRIP relay.
Range: Energized, De-energized
Force the 6 AUXILIARY relay state as per the 1 TRIP relay.
Range: Energized, De-energized
Force the 7 AUXILIARY relay state as per the 1 TRIP relay.
Range: Energized, De-energized
Force the 8 SELF-TEST WARNING relay state as per the 1 TRIP relay.
Range: Energized, De-energized
Force the solid state output as per the 1 TRIP relay.
750/760 Feeder Management Relay
15.1 OUTPUT RELAYS
15.1.1 DESCRIPTION
15.1.2 SETPOINTS