Iii.4 Power Quality Of A 1 Phase 3 Wire (1P3W) System - PCE Instruments PCE-830 User Manual

Table of Contents

Advertisement

III.4 Power Quality of a 1 Phase 3 Wire (1P3W) System

POWER
a. Turn the power on. Press the POWER and the 1Φ3Φ buttons to select
the 1P3W system. The type of system will be displayed at the bottom
right of the LCD.
b. Connect the three test leads to the voltage terminals L1, L2 and V
(Neutral) of the system.
c.
Connect the two current probes to the power analyzer input terminal I1
and I2.
d. Clamp on to the L1 and L2. Make sure the current flows from the front of
the current probe to the back of it.
e. All parameters of the system will be shown in LCD
For the meaning of each parameter, refer to XIV. NOMENCLATURE.
1 3W
I
1
V
1N
N
V
2N
I
2
100A
(HARMON)
100A
(POWER)
60A
(HARMON)
10A
1A
20
100A
(HARMON)
100A
(POWER)
60A
(HARMON)
10A
1A
N

Advertisement