VI. SET THE CT AND VT RATIO
Press the SETUP button several times until CT or VT is shown in reverse video.
Press the ▲ or ▼ button to increment or decrement the value by 1. Holding the
▲ or ▼ button will speed up the process of incrementing or decrementing. To
exit, press the EXIT button.
The range of CT ratio is from 1 to 600. The range of VT ratio is from 1 to 3000.
Once the CT or VT is set, the voltage and current readings becomes
CURRENT (displayed) = CURRENT (measured) x CT Ratio
VOLTAGE (displayed) = VOLTAGE (measured) x VT Ratio