APAX-5045 Specifications
Digital Input
Channels: 12
Points per Common: 12
Type: Sink/Source (Wet Contact)
Input Voltage Rated Value: 24 VDC
For "0" signal: -5 ~ 5 VDC
For "1" signal: 15 ~ 30 VDC and -15 ~ -30 VDC
Input Impedance: 5.4 k
Input Current: typical 4.4 mA (At signal "1")
Input Filter: 3 ms
Input Characteristic Curve: According to IEC 61131-2, type 1