Application Wiring
APAX-5013 Technical Specifications
Channels: 8
Input Impedance: >10 M
Input Type: Pt-100, Pt-200, Pt-500, Pt-1000, Balco, Ni 518 RTD (2-wire and 3-wire)
Temperature Range: Pt-100,Pt-200,Pt-500,Pt-1000: -120~130C, -200~850C
Supports IEC 60751 ITS90 (0.03851// C) and JIS C 1604 (0.03916 // C)
Balco 500: -30 ~ 120 C
Ni 518: -80 ~ 100 C, 0 ~ 100 C
Configure Different Range for Each Channel: Yes
Resolution: 16-bit
Accuracy: ±0.1 % of FSR (at 25 C)
Sampling Rate: 50 Hz filter: 8 sample/second (total)
CMR @ 50/60 Hz: 90 dBs
NMR @ 50/60 Hz: 60 dBs
Noise Suppression for Frequency: 50/60 Hz
Span Drift: 15 ppm/ C
Input Characteristic Curve: According to IEC 61131-2
Wire Burnout Detection: All RTD type
Protection
Isolation: 2,500 VDC (Between channels and backplane)
Environment
Operating Temperature: -10 ~ 60 C (when mounted vertically)
Storage Temperature: -40 ~ 70 C
Relative Humidity: 5 ~ 95% (non-condensing)
General
Dimensions (W x H x D): 30 x 139 x 100 mm
Weight: 170 g
Power Consumption: 2.5 W @ 24 VDC (typical)

Figure 2.2 Wiring for APAX-5013

60 Hz filter: 10 sample/second (total)
27