Pulse/DIR, With Reload, Count Repetitively, DI Gate Enable, Falling Edge,
Retriggerable
Figure 3.38 shows pulse/direction mode, Ch0_A provides the counting function, one
pulse, one count. Ch0_B provides the clockwise and counter clockwise function.
When the counter0 is enabled, the couner0 starts to count. If the counter value is
overflow or underflow, it will reset to the defined value (e.g. 0x33) and keep counting
repetitively. If the DI0 status is falling edge, the counter0 will starts to count and can
be retriggered. Otherwise, the counter0 will stop counting.
Ch0_A
Ch0_B
Up
Counter0
Enable
DI0
Counter 0
0x33
0x34
Value
Counter0
Underflow
Ch0_A
Ch0_B
Down
Counter0
Enable
DI0
Counter 0
0x33
0x32
Value
Counter0
Overflow
Figure 3.53 Pulse/DIR, With Reload, Count Repetitively, DI Gate Enable, Falling
Down
......
0x33
0x32
0x00
Up
......
0x33
0x34
0xF..F
Edge, Retriggerable
97
APAX-5000 I/O Series User Manual
0x33
0x32
0x31
0x30
0x33
0x34
0x35
0x36