Advantech APAX-5013 User Manual page 37

Apax-5000 series
Hide thumbs Also See for APAX-5013:
Table of Contents

Advertisement

Note!
To keep measurement accuracy please short the channels that
are not in use.
Note!
You can use the jumpers to configure each analog input channel type
(voltage or current). Refer to Section 1.5 for the location of the jumpers.
There are a total of 12 jumpers and each is specific for one channel.
Technical Specifications of APAX-5017
Channels: 12 (Differential)
Input Impedance: >10 M (Voltage), 120 (Current)
Input Type: V, mV, mA
Voltage/Current Range:
±150mV,±500mV,±1V,±5V,±10V,±20mA,0~20mA,4~20 mA
Configure Different Range for Each Channel: Yes
Accuracy: ±0.1% or better (Voltage), ±0.2% or better (Current) at 25 C
Resolution:
Voltage
Range
Resolution
±150 mV
16 bit
±500 mV
16 bit
±1 V
16 bit
±5 V
16 bit
±10 V
16 bit
Current
Range
Resolution
±20 mA
15 bit
0 ~ 20 mA
14 bit
4 ~ 20 mA
14 bit
Note!
Please base on 16 bit to convert your raw data to engineer unit in the
current mode.
Sampling Rate: 12 samples/second (total)
CMR @ 50/60 Hz: 90 dB
NMR @ 50/60 Hz: 67 dB
Noise Suppression for Frequency: 50/60 Hz
Span Drift: ±30 ppm/ C
Zero Drift: ±6 V/ C
Input Characteristic Curve: According to IEC 61131-2
Common Mode Voltage: up to 200 VDC
Wire Burnout Detection: Only for 4 ~ 20 mA range
29
APAX-5000 I/O User Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Apax-5028Apax-5017Apax-5017hApax-5018Apax-5017pe

Table of Contents