Output Parameters Of Pid_Compact V1 - Siemens SIMATIC S7-1200 Function Manual

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

9.1.5.3

Output parameters of PID_Compact V1

Table 9- 5
Output parameters of PID_Compact V1
Parameter
Data type
ScaledInput
REAL
Outputs "Output", "Output_PER", and "Output_PWM" can be used concurrently.
Output
REAL
Output_PER
WORD
Output_PWM
BOOL
SetpointLimit_H
BOOL
SetpointLimit_L
BOOL
InputWarning_H
BOOL
InputWarning_L
BOOL
State
INT
Error
DWORD
PID control
Function Manual, 03/2017, A5E35300227-AC
Default
Description
0.0
Output of the scaled process value
0.0
Output value in REAL format
W#16#0
Analog output value
FALSE
Pulse-width-modulated output value
The output value is formed by minimum On and Off times.
FALSE
If SetpointLimit_H = TRUE, the setpoint absolute high limit is
reached. The setpoint in the CPU is limited to the configured setpoint
absolute high limit. The configured process value absolute high limit
is the default for the setpoint high limit.
If you set sPid_Cmpt.r_Sp_Hlm to a value within the process value
limits, this value is used as the setpoint high limit.
FALSE
If SetpointLimit_L = TRUE, the setpoint absolute low limit has been
reached. In the CPU, the setpoint is limited to the configured setpoint
absolute low limit. The configured process value absolute low limit is
the default setting for the setpoint low limit.
If you set sPid_Cmpt.r_Sp_Llm to a value within the process value
limits, this value is used as the setpoint low limit.
FALSE
If InputWarning_H = TRUE, the process value has reached or ex-
ceeded the warning high limit.
FALSE
If InputWarning_L = TRUE, the process value has reached or fallen
below the warning low limit.
0
The State parameter (Page 293) shows the current operating mode
of the PID controller. To change the operating mode, use variable
sRet.i_Mode.
State = 0: Inactive
State = 1: pretuning
State = 2: fine tuning
State = 3: Automatic mode
State = 4: Manual mode
W#16#0
The Error parameter (Page 297) indicates the error messages.
Error = 0000: No error pending.
Instructions
9.1 PID_Compact
287