Instructions
9.2 PID_3Step
ErrorBits
Description

 ( DW#16#...)
0200
Invalid value at "Input" parameter: Value has an invalid number format.
If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_3Step
switches to "Approach substitute output value with error monitoring" or "Error monitoring" mode. As
soon as the error is no longer pending, PID_3Step switches back to automatic mode.
If pretuning, fine tuning, or transition time measurement mode and ActivateRecoverMode = TRUE were
active before the error occurred, PID_3Step switches to the operating mode that is saved in the Mode
parameter.
0400
Calculation of output value failed. Check the PID parameters.
If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_3Step
switches to "Approach substitute output value with error monitoring" or "Error monitoring" mode. As
soon as the error is no longer pending, PID_3Step switches back to automatic mode.
If pretuning, fine tuning, or transition time measurement mode and ActivateRecoverMode = TRUE were
active before the error occurred, PID_3Step switches to the operating mode that is saved in the Mode
parameter.
0800
Sampling time error: PID_3Step is not called within the sampling time of the cyclic interrupt OB.
If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_3Step
remains in automatic mode.
If pretuning, fine tuning, or transition time measurement mode and ActivateRecoverMode = TRUE were
active before the error occurred, PID_3Step switches to the operating mode that is saved in the Mode
parameter.
If this error occurred during simulation with PLCSIM, see the notes under Simulating PID_3Step V2 with
PLCSIM (Page 137).
1000
Invalid value at "Setpoint" parameter: Value has an invalid number format.
If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_3Step
switches to "Approach substitute output value with error monitoring" or "Error monitoring" mode. As
soon as the error is no longer pending, PID_3Step switches back to automatic mode.
If pretuning, fine tuning, or transition time measurement mode and ActivateRecoverMode = TRUE were
active before the error occurred, PID_3Step switches to the operating mode that is saved in the Mode
parameter.
2000
Invalid value at Feedback_PER parameter.
Check whether an error is pending at the analog input.
The actuator cannot be moved to the substitute output value and remains in its current position. In man-
ual mode, you can change the position of the actuator only with Manual_UP and Manual_DN, and not
with ManualValue.
If automatic mode was active before the error occurred, ActivateRecoverMode = TRUE, and the error is
no longer pending, PID_3Step switches back to automatic mode.
If pretuning, fine tuning, or transition time measurement mode and ActivateRecoverMode = TRUE were
active before the error occurred, PID_3Step switches to the operating mode that is saved in the Mode
parameter.
4000
Invalid value at Feedback parameter. Value has an invalid number format.
The actuator cannot be moved to the substitute output value and remains in its current position. In man-
ual mode, you can change the position of the actuator only with Manual_UP and Manual_DN, and not
with ManualValue.
If automatic mode was active before the error occurred, ActivateRecoverMode = TRUE, and the error is
no longer pending, PID_3Step switches back to automatic mode.
If pretuning, fine tuning, or transition time measurement mode and ActivateRecoverMode = TRUE were
active before the error occurred, PID_3Step switches to the operating mode that is saved in the Mode
parameter.
336
Function Manual, 03/2017, A5E35300227-AC