9.3 PID_Temp
Parameter
Data type Default
SetpointLimit_L BOOL
InputWarning
BOOL
_H
InputWarning
BOOL
_L
State
INT
Error
BOOL
ErrorBits
DWORD
392
Description
FALSE
If SetpointLimit_L = TRUE, the absolute setpoint low limit is reached (Set-
point ≤ Config.SetpointLowerLimit) or Setpoint ≤ Config.InputLowerLimit.
The setpoint low limit is the maximum of Config.SetpointLowerLimit and Con-
fig.InputLowerLimit.
FALSE
If InputWarning_H = TRUE, the process value has reached or exceeded the
warning high limit (ScaledInput ≥ Config.InputUpperWarning).
FALSE
If InputWarning_L = TRUE, the process value has reached or fallen below the
warning low limit (ScaledInput ≤ Config.InputLowerWarning).
0
The PID_Temp state and mode parameters (Page 430) shows the current
operating mode of the PID controller. You can change the operating mode
using the input parameter Mode and a rising edge at ModeActivate. For pre-
tuning and fine tuning, you specify with Heat.EnableTuning and
Cool.EnableTuning whether tuning takes place for heating or cooling.
State = 0: Inactive
State = 1: Pretuning
State = 2: Fine tuning
State = 3: Automatic mode
State = 4: Manual mode
State = 5: Substitute output value with error monitoring
FALSE
If Error = TRUE, at least one error message is pending in this cycle.
DW#16#0
The PID_Temp ErrorBits parameter (Page 439) shows the pending error
messages.
ErrorBits is retentive and is reset with a rising edge at Reset or ErrorAck.