Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Tag
Config.SetpointUpperLimit
Config.SetpointLowerLimit
Config.ActivateCooling
PID control
Function Manual, 03/2017, A5E35300227-AC
Data type
Default
REAL
3.402822e+38
REAL
-3.402822e+38 Low limit of the setpoint
BOOL
FALSE
Description
High limit of setpoint
Setpoint and SubstituteSetpoint are monitored to ensure
adherence to this limit. If the limit is exceeded, a warning
is output at the Warning parameter.
If you configure SetpointUpperLimit outside the pro-
cess value limits, the configured absolute process val-
ue high limit is used as the setpoint high limit.
If you configure SetpointUpperLimit within the process
value limits, this value is used as the setpoint high lim-
it.
SetpointUpperLimit > SetpointLowerLimit
Setpoint and SubstituteSetpoint are monitored to ensure
adherence to this limit. If the limit is undershot, a warning
is output at the Warning parameter.
If you set SetpointLowerLimit outside the process val-
ue limits, the configured process value absolute low
limit is used as the setpoint low limit.
If you configure SetpointLowerLimit within the process
value limits, this value is used as the setpoint low limit.
SetpointLowerLimit < SetpointUpperLimit
Activate cooling output
Config.ActivateCooling = FALSE
Only the outputs for heating are used.
Config.ActivateCooling = TRUE
The outputs for heating and cooling are used.
If you are using the cooling output, the controller must not
be configured as master controller (Con-
fig.Cascade.IsMaster must be FALSE) .
Instructions
9.3 PID_Temp
401