Input Parameters Of Polyline; Output Parameters Of Polyline - Siemens SIMATIC S7-1200 Function Manual

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Instructions
9.5 Polyline
9.5.4

Input parameters of Polyline

Parameter
Data type
Input
REAL
Substitute-
REAL
Output
Validate
BOOL
ErrorAck
BOOL
Reset
BOOL
9.5.5

Output parameters of Polyline

Parameter
Data type
Output
REAL
Error
BOOL
ErrorBits
DWORD
516
Default
Description
0.0
Input value
0.0
SubstituteOutput is used as the substitute output value when
Reset = TRUE
or
An error with error message ErrorBits ≥ 16#0001_0000 prevents correct
calculation of the interpolation result, and the configured value of Error-
Mode is 1 .
FALSE
If Validate is set to TRUE, the polyline data in UserData is checked for validity
and transferred to WorkingData.
FALSE
Deletes the error messages
Edge FALSE -> TRUE
ErrorBits is reset
FALSE
Performs a restart of the instruction
Edge FALSE -> TRUE
ErrorBits is reset.
As long as Reset is set to TRUE, the substitute output value Substitute-
Output is output at the output.
As long as Reset is set to FALSE, the interpolation calculation is per-
formed.
Default
Description
0.0
Output value
FALSE
When Error is set to TRUE, at least one error is currently pending.
DW#16#0
The ErrorBits parameter (Page 518) shows which error messages are pend-
ing. ErrorBits is retentive and is reset at a positive edge at Reset or ErrorAck .
Function Manual, 03/2017, A5E35300227-AC