9.4.5.7

Static variables TCONT_S

Table 9- 26
Static variables TCONT_S
Parameters
Ad-
Data
dress
type
PV_FAC
32.0
REAL
PV_OFFS
36.0
REAL
DEADB_W
40.0
REAL
PFAC_SP
44.4
REAL
GAIN
48.0
REAL
TI
52.0
REAL
MTR_TM
56.0
REAL
PULSE_TM
60.0
REAL
BREAK_TM
64.0
REAL
PER_MODE 68.0
INT
PVPER_ON
70.0
BOOL
See also
Block diagram TCONT_S (Page 501)
PID control
Function Manual, 03/2017, A5E35300227-AC
Default
Description
1.0
The "Process value factor" input is multiplied by the process value. The input
is used to scale the process value range.
0.0
The input "Process value offset" is added to the process value. The input is
used to scale the process value range.
The valid values depend on the sensors used.
0.0
A deadband is applied to the control deviation. The "Deadband width" input
determines the size of the deadband.
DEADB_W ≥ 0.0
1.0
PFAC_SP specifies the effective P-action when there is a setpoint change.
1: P-action has full effect if the setpoint changes.
0: P-action has no effect if the setpoint changes.
Values from 0.0 to 1.0 are permitted.
2.0
The "Proportional gain" input specifies controller amplification. The direction of
control can be reversed by giving GAIN a negative sign.
%/phys. unit
40.0 s
The "Integration time" (integral-action time) input defines the integrator's time
response.
30 s
The runtime from endstop to endstop of the control valve is entered at the
"Motor actuating time" parameter.
MTR_TM ≥ CYCLE
0.0 s
A minimum pulse time can be configured at the "Minimum pulse time" param-
eter.
0.0 s
You can assign a minimum break time at the parameter "Minimum break
time".
0
You can use this switch to enter the type of I/O module. The process value at
input PV_PER is then scaled as follows at the PV output.
PER_MODE = 0: Thermoelements; PT100/NI100; standard
PV_PER * 0.1
Unit: °C, °F
PER_MODE = 1: PT100/NI100; climate
PV_PER * 0.01
Unit: °C, °F
PER_MODE = 2: Current/voltage
PV_PER * 100/27648
Unit: %
FALSE
If the process value is to be read in from the I/Os, the PV_PER input must be
interconnected with the I/Os and the "Enable process value I/Os" input must
be set.