Siemens SIMATIC S7-1200 Function Manual page 409

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Tag
Config.Output.Cool.PidLower-
Limit
Config.Output.Cool.Upper-
Scaling
Config.Output.Cool.Lower-
Scaling
Config.Output.Cool.PwmUpper-
Scaling
PID control
Function Manual, 03/2017, A5E35300227-AC
Data type
Default
REAL
-100.0
REAL
100.0
REAL
0.0
REAL
100.0
Description
Low limit of the PID output value for cooling
For controllers with activated cooling output (Con-
fig.ActivateCooling = TRUE), the PID output value (Pi-
dOutputSum) is limited to this low limit.
Cool.PidLowerLimit forms a value pair together with the
following parameters for scaling of the PID output value
(PidOutputSum) to the outputs for cooling:
Cool.UpperScaling for OutputCool
Cool.PwmUpperScaling for OutputCool_PWM
Cool.PerUpperScaling for OutputCool_PER
If you want to limit the value at the associated output, you
must also adjust these scaling values.
Only effective if the cooling output is activated (Config
.ActivateCooling = TRUE).
Cool.PidLowerLimit < Cool.PidUpperLimit
Scaled high output value for cooling
Cool.UpperScaling and Cool.PidLowerLimit form a value
pair for scaling of the PID output value (PidOutputSum) to
the output value for cooling (OutputCool).
The OutputCool value is always located between
Cool.UpperScaling and Cool.LowerScaling.
Only effective if the cooling output is activated (Config
.ActivateCooling = TRUE).
Cool.UpperScaling ≠ Cool.LowerScaling
Scaled low output value for cooling
Cool.LowerScaling and Cool.PidUpperLimit form a value
pair for scaling of the PID output value (PidOutputSum) to
the output value for cooling (OutputCool).
The OutputCool value is always located between
Cool.UpperScaling and Cool.LowerScaling.
Only effective if the cooling output is activated (Config
.ActivateCooling = TRUE).
Cool.UpperScaling ≠ Cool.LowerScaling
Scaled high PWM output value for cooling
Cool.PwmUpperScaling and Cool.PidLowerLimit form a
value pair for scaling of the PID output value (PidOut-
putSum) to the pulse-width modulated output value for
cooling (OutputCool_PWM).
The OutputCool_PWM value is always located between
Cool.PwmUpperScaling and Cool.PwmLowerScaling.
Cool.PwmUpperScaling is only effective if the cooling
output is activated (Config.ActivateCooling = TRUE) and
OutputCool_PWM is selected as output for cooling
(Cool.Select = 1).
100.0 ≥ Cool.PwmUpperScaling ≥ 0.0
Cool.PwmUpperScaling ≠ Cool.PwmLowerScaling
Instructions
9.3 PID_Temp