Tag
PIDSelfTune.TIR.State
PIDSelfTune.TIR.ProcPar-
HeatOk
PIDSelfTune.TIR.ProcPar-
CoolOk
PID control
Function Manual, 03/2017, A5E35300227-AC
Data type
Default
INT
0
BOOL
FALSE
BOOL
FALSE
Description
The TIR.State tag indicates the current phase of "fine
tuning":
State = 0: Initialize fine tuning
State = 100: Calculate standard deviation for heating
State = 200: Calculate standard deviation for cooling
State = 300: Attempting to reach setpoint for heating
with two-step control using heating
State = 400: Attempting to reach setpoint for cooling
with two-step control using cooling
State = 500: Attempting to reach setpoint for heating
with PID control
State = 600: Attempting to reach setpoint for cooling
with PID control
State = 700: Calculate standard deviation for heating
State = 800: Calculate standard deviation for cooling
State = 900: Determine oscillation and calculate pa-
rameters for heating
State = 1000: Determine oscillation and calculate pa-
rameters for cooling
State = 9900: Fine tuning successful
State = 1: Fine tuning not successful
TRUE: The calculation of the process parameters for fine
tuning heating was successful.
This tag is set during tuning.
It must be met for calculation of the PID parameters for
heating.
TRUE: The calculation of the process parameters for fine
tuning cooling was successful.
This tag is set during tuning.
It must be met for calculation of the PID parameters for
cooling.