Siemens SIMATIC S7-1200 Function Manual page 262

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Instructions
9.1 PID_Compact
Tag
Retain.CtrlParams.DWeighting
Retain.CtrlParams.Cycle
Note
Change the tags listed in this table in "Inactive" mode to prevent malfunction of the PID
controller.
See also
Tag ActivateRecoverMode V2 (Page 271)
Tag Warning V2 (Page 273)
Downloading technology objects to device (Page 44)
262
Data type
Default
REAL
1.0
REAL
1.0
Description
Active derivative action weighting
The derivative action may weaken with changes to the
setpoint.
Values from 0.0 to 1.0 are applicable.
1.0: Derivative action is fully effective upon setpoint
change
0.0: Derivative action is not effective upon setpoint
change
The derivative action is always fully effective when the
process value is changed.
DWeighting is retentive.
Active sampling time of the PID algorithm
CtrlParams.Cycle is calculated during tuning and
rounded to an integer multiple of CycleTime.Value.
CtrlParams.Cycle is used as time period of the pulse
width modulation.
Cycle is retentive.
Function Manual, 03/2017, A5E35300227-AC