Input Parameter Cont_C - Siemens SIMATIC S7-1200 Function Manual

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

9.4.1.4

Input parameter CONT_C

Table 9- 13
Input parameter CONT_C
Parameters
Data
type
COM_RST
BOOL
MAN_ON
BOOL
PVPER_ON
BOOL
P_SEL
BOOL
I_SEL
BOOL
INT_HOLD
BOOL
I_ITL_ON
BOOL
D_SEL
BOOL
CYCLE
TIME
SP_INT
REAL
PV_IN
REAL
PV_PER
WORD W#16#0000 The process value in I/O format is interconnected with the controller at the "Process
MAN
REAL
GAIN
REAL
TI
TIME
TD
TIME
TM_LAG
TIME
DEADB_W
REAL
PID control
Function Manual, 03/2017, A5E35300227-AC
Default
Description
FALSE

 T he instruction has an initialization routine that is 
 p rocessed when the "Restart"
input is set.
TRUE
If the input "Enable manual mode" is set then the control loop is interrupted. A
manual value 
 i s set as the manipulated value.
FALSE
If the process value is to be read in from the I/Os, the PV_PER input must be inter-
connected with the I/Os and the "Enable process value I/Os" input must be set.
TRUE
The PID actions can be switched on and off individually in the PID algorithm. P-
action is on when the "Enable P-action" input is set.
TRUE
The PID actions can be switched on and off individually in the PID algorithm. I ac-
tion is on when the input 
 " I-action on" is set.
FALSE
The output of the integral action can be frozen. For this the input "I-action hold"
must be set.
FALSE
The output of the integral action can be set at the I_ITLVAL input. For this the input
"Set I-action" must be set.
FALSE
The PID actions can be switched on and off individually in the PID algorithm. D-
action is on when the 
 i nput "Enable D-action" is set.
T#1s
The time between block calls must be constant. The "Sampling time" input specifies
the 
 t ime between block calls.
CYCLE >= 1ms
0.0
The input "Internal setpoint" is used to specify a setpoint.
Permissible are values from -100 to 100 % or a physical variable 1).
0.0
At the "Process value input" you can assign parameters to a commissioning value
or you can interconnect an external process value in floating-point format.
Permissible are values from -100 to 100 % or a physical variable 1).
value I/0" input.
0.0
The "Manual value" input is used to set a 
 m anual value using the operator interface

 f unctions.
Permissible are values from -100 to 100 % or a physical variable 2).
2.0
The "Proportional gain" input specifies controller amplification.
T#20s

 T he "Integration time" input determines the time 
 r esponse of the integral action.
TI >= CYCLE
T#10s

 T he "Derivative action time" input determines the time 
 r esponse of the derivative
action.
TD >= CYCLE
T#2s
Time lag of the D-action
The algorithm of the D-action contains a delay for which parameters can be as-
signed at the input "Time lag of the D-action".
TM_LAG >= CYCLE/2
0.0
A dead band is applied to the system deviation. The "Dead band width" input de-
termines the size of the dead band.
DEADB_W >= 0.0 (%) or a physical variable 1)