VISTA-128BP/VISTA-250BP Installation and Setup Guide
Features
Hardwire and Optional Expansion Zones
•
Provides 9 hardwire zones.
•
Supports up to 16 2-wire smoke detectors on zone 1.
•
Automatically resets 4-wire smoke detectors using the J7 output when a code + off is entered.
•
Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm.
This feature requires a 4204 Relay Module and/or the 333PRM.
•
Provides tamper supervision on the hardwire zones.
•
Supports up to 50 2-wire latching glassbreak detectors on zone 8.
•
Supports up to 241 additional expansion zones (119 for the VISTA-128BP) using a built-in polling (multiplex) loop.
•
Supports up to 250 wireless zones (128 for the VISTA-128BP) (fewer if using hardwire and/or polling loop zones).
The 5881ENHC RF Receiver and the 5869 Holdup Switch Transmitter are listed for UL Commercial Burglary
U L
applications. All other RF receivers and transmitters are not listed for UL Commercial Burglary applications.
•
Can program burglary zones as silent in the alarm condition (alarm output is silent and the keypad does not
display or sound the alarm).
•
Provides three keypad panic keys: 1 + ✴ (A), ✴ + # (B), and 3 + # (C).
Peripherals Devices
•
Supports up to 31 addressable devices, (keypads, RF receivers, relay modules, etc.).
•
Supervises devices (keypads, RF receivers, and relay modules) and individual relays (up to 32), as well as system
zones (RF receivers and keypad panics).
•
Provides 96 outputs using 4204 and 4204CF Relay Modules, Fire System Annunciators (FSA-8, FSA-24), V-Plex
Relay Modules and X-10 devices can activate outputs in response to system events (alarm condition), at a specific
time of day, at random times, and manually using the #70 Relay Command Mode.
•
Supports the ADEMCO 4285/4286 VIP Module, which allows access to the system from either a remote location or
on the premises
U L
The VIP Module is not Listed for use with the VISTA-128BP/VISTA-250BP Control Panel in a UL installation.
•
Supports the ADEMCO 4146 Keyswitch on any one of the system's 8 partitions.
Arming/Disarming and Bypassing
•
Can arm the system with zones faulted (Vent Zone). These zones are automatically bypassed and can be
programmed to automatically unbypass when the zone restores.
•
Can arm with entry/exit and interior type zones faulted (Arm w/Fault). These zones must be restored before the
exit delay expires, otherwise an alarm is generated.
•
Vent zones cannot be used in UL installations.
U L
•
You must disable the Force Arm option (used in conjunction with the Arm w/Fault option), in UL installations.
•
Provides global arming capability (ability to arm all partitions the user code has access to in one command).
•
Can Quick Exit an armed premises without having to disarm and then rearm the system.
U L
Quick Exit is not permitted for use with the VISTA-128BP/VISTA-250BP Control Panel in a UL installation.
1-2