VISTA-128BP/VISTA-250BP Installation and Setup Guide
Downloading
Supports upload and download capability.
Can perform unattended downloading (no one at the downloading computer).
Provides an Installer Unattended Program Mode. This allows the installer to program the download phone
number, subscriber number, and primary central station receiver phone number without entering the normal
program mode.
Can periodically and automatically perform a scheduled download.
U L
Unattended and Scheduled Downloading are not UL Listed features.
Can download access control cardholder information.
Event Log
Provides an event log (history log) that can store up to 1000 events.
Can print the event log on a parallel or serial printer using a VA8201 Alpha Pager Module.
Can view the event log on an alpha keypad or AUI.
Additional Features
Provides up to 60 installer-defined, custom words that can be used for zone descriptors.
Provides 32 keypad macro commands (each macro is a series of keypad commands of up to 32 keystrokes) using
the A, B, C, and D keys by partition.
Provides cross-zone capability, which helps prevent false alarms by preventing a zone from going into alarm
unless its cross-zone is also faulted within a 5-minute period.
Contains a built-in User's Manual, which provides the end user with a brief explanation of the function of a key
when the user presses any of the function keys on the keypad for 5 seconds.
Provides trigger outputs, which may interface with Long Range Radio equipment or other devices such as
keyswitch LEDs, printer, or pager.
Provides an RS232 input for serial data. This is useful for interfacing the system with Automation software.
Automation software cannot be used if a serial printer is used on the system.
At least one 2-line alpha keypad (6139/6160) must be connected to the system for programming (if you are using
keypad programming), and must remain connected to the system in order to allow the primary user to program
additional user codes into the system at a later time.
1-4
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM