Installing A 4100Sm; Figure 3-32: Wiring The Vista Gateway Module; Figure 3-33: 4100Sm Using A Serial Printer - Honeywell VISTA-128BP Installation And Setup Manual

Commercial burglary partitioned security systems
Hide thumbs Also See for VISTA-128BP:
Table of Contents

Advertisement

The VGM then reformats and retransmits this
information to the Main Logic Board, (MLB) on the
PassPoint ACS network bus.
Interfacing the VISTA-128BP/VISTA-250BP
U L
with the PassPoint Access Control System via
the VISTA Gateway Module is not permissible
for UL installations.
Wiring the VISTA Gateway Module
The VISTA Gateway Module is connected between the
ECP bus (VISTA-128BP/VISTA-250BP keypad
terminals) and the network bus of the PassPoint
Access Control System. See Figure 3-32 for the proper
wiring connections.

Installing a 4100SM

The 4100SM is used to print event log reports to a
serial printer or to interface the control with a
computer equipped with Home Automation software.
When using the 4100SM, the system can
interface with either a serial printer or Home
Automation. It cannot do both.
NOTE: See SECTION 4: Programming for the
programming details when using the 4100SM.
Printer/Computer Configurations
Configure the serial printer or the Home Automation
computer as follows:
8 data bits, no parity, 1 stop bit
1200 baud
Connecting the 4100SM to a Serial Printer
To connect a serial printer using the 4100SM, refer to
Figure 3-33and perform the following steps:
Action
Step
Connect terminal 1 on the 4100SM to the
1
Violet wire on the 4142TR cable.
Connect terminal 6 on the 4100SM to the
2
Brown wire on the 4142TR cable.
Connect the 4142TR cable to J8 on the
3
control.
Connect terminals 8 and 7 of the 4100SM to
4
terminals 6 and 7 (aux. power (+) and (-)),
respectively of the control.
Connect the UL EDP Listed serial printer to
5
the 4100SM Interface Module.
The 4100SM Module is supplied with a 10-
foot RS232 cable. A longer cable can be used
if the VISTA-128BP/VISTA-250BP is
separated from the serial printer by more
than 10 feet, but the total cable length
should be less than 50 feet.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Section 3 - Installing the Control
PROM C
TRANSFORMER

Figure 3-32: Wiring the VISTA Gateway Module

1
2
3
4
5
6
7
8
NU
To TB6 Aux. Power (+)
To TB7 Aux. Power (-)
4100SM JUMPERS
(CUT TO SET RESPECTIVE SIGNAL FLOATING)
COLOR
FUNCTION
PIN #
RED
CD
8
BLUE
CTS
5
WHITE
DSR
6

Figure 3-33: 4100SM Using a Serial Printer

NOTE: See the 4100SM Installation Instructions for
details concerning the serial printer operation.
Connecting the 4100SM to a Home Automation
Computer
To connect the computer to the 4100SM, refer to
Figure 3-34 and perform the following steps:
Action
Step
Connect terminal 23 on the control panel to
1
terminal 3 on the 4100SM.
Connect terminal 6 on the 4100SM to the
2
Brown wire on the 4142TR cable.
Connect the 4142TR cable to J8 on the
3
control.
Connect terminals 8 and 7 of the 4100SM to
4
terminals 6 and 7 (aux. power (+) and (-)),
respectively of the control.
Connect the Home Automation computer
5
serial port to the 4100SM Interface Module.
}
ECHELON NETWORK
(PASSPOINT ACS)
4-PIN
KEYPAD
PLUG
GREEN
}
TO
BLACK
CONTROL'S
RED
KEYPAD
TERMINALS
YELLOW
9
J8 CONNECTOR
4142TR CABLE (SUPPLIED WITH 4100SM)
4100SM SERIAL MODULE
8
+ PWR
(25mA current draw)
7
- (GND)
6
RXD
5
not used
4
not used
3
TXD
2
not used
1
DTR
RED
BLUE
USE GENDER CHANGER
3M
Cable
SUPPLIED WITH 4100SM
Supplied with
IF PRINTER HAS DB25
4100SM
MALE CONNECTOR
SERIAL PRINTER
SET FOR: 8 DATA BITS
EVEN PARITY
STOP BIT
300/1200 BAUD
WHITE
3-27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-250bpVista-128sia

Table of Contents