Section 1: General Description; Sia Installations; About The Vista-128Fbpt/Vista-250Fbpt; Features - Honeywell VISTA-250FBPT Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-250FBPT:
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

SIA Installations

The VISTA-128FBPT and VISTA-250FBPT are not certified as SIA compliant, but can be programmed for False Alarm
Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields

About the VISTA-128FBPT/VISTA-250FBPT

The VISTA-128FBPT and VISTA-250FBPT are 8-partition, UL Listed commercial fire and burglary control panels that
include the features described below.
NOTE: All sections of this manual reference the capacities of the VISTA-250FBPT when describing system
features. Please note the differences between the VISTA-128FBPT and VISTA-250FBPT in the table below.
All other features are identical.
Number of Zones
Number of User Codes
Event Log Capacity
Number of Access Cards

Features

Hardwire and Optional Expansion Zones
Provides 8 hardwire zones.
Supports up to 16 2-wire smoke detectors each on zone 1 and zone 2 (32 total).
Automatically resets 4-wire smoke detectors if the Aux Relay is programmed for smoke reset (3*61 = 2).
Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm.
This feature requires a System Sensor RRS-MOD.
Supports up to 242 additional expansion zones (120 for the VISTA-128FBPT) using a built-in polling (V-Plex)
loop.
Supports up to 250 wireless zones (128 for the VISTA-128FBPT) fewer if using hardwire and/or polling loop
zones.
U LC
Wireless devices are not ULC Listed for and cannot be used in ULC Installations.
Peripheral Devices
Supports up to 31 addressable devices, (keypads, RF receivers, relay modules, etc.).
Supervises devices (keypads, RF receivers, and relay modules) and individual relays (up to 32), as well as
system zones.
Keypads
6160CR2 keypads for Fire applications
6160 keypads for Burglary applications
(Alpha keypads provide three panic key functions: 1 + ∗ (A), ∗ + # (B), and 3 + # (C).)
Up to six 6280 Graphic/Touch-Screen keypads for burglary applications.
AlarmNet Total Connect (Remote Interactive Service) allows access from a wireless smart phone or web browser
via any Total Connect 2 compatible AlarmNet device.
U L
Use of Remote Interactive Service (Total Connect) is not permitted in UL installations.
NOTE: If using Total Connect Remote Interactive Services, the virtual keypad must be assigned to a burglary partition,
and the GOTO feature (program field 2∗18) must be "0" (disabled) for partition 1 (the fire partition) so that the Fire
system cannot be accessed remotely. This is the system default setting.

Section 1: General Description

Feature
VISTA-128FBPT
128
150
512
250
11
VISTA-250FBPT
250
250
1000
500
.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-128fbpt

Table of Contents