High Elevation; Gas Line Installation; Gas Pipe Pressure Testing; I.t. Valve Description - Regency Fireplace Products Liberty LRI4E-NG Owners & Installation Manual

Gas
Table of Contents

Advertisement

LRI4E-NG / HRI4E-NG
SYSTEM DATA
Min. Supply Pressure 5" WC (1.25 kpa)
Manifold Pressure
3.5" WC (0.87 kpa)
Oriice Size
#35 DMS
Maximum Input
31,000 Btu/h
(9.09 kW)
LRI4E-LP / HRI4E-LP
SYSTEM DATA
Min. Supply Pressure
11" WC (2.73 kpa)
Manifold Pressure
10" WC (2.49 kpa)
Oriice Size
#53 DMS
Maximum Input
31,000 Btu/h
(9.09 kW)

HIGH ELEVATION

This unit is approved for altitude 0 to 4500 ft. (CAN1
2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or lex connectors use only
approved ittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and lex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open flame for leak testing.
Burner
Pilot
Note: If you have an incorrect lame pattern,
contact your Regency
instructions.
Incorrect flame pattern will have small, probably
yellow flames, not coming into proper contact
with the rear burner or flame sensor.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide lat screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits speciied on the safety label.
6) When inished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" lat screwdriver.
Note: Screw should be snug, but do not over
tighten.
885 S.I.T. VALVE
DESCRIPTION
Flame Sensor
1) 6 Stage lame adjustment
2) Pilot adjustment
3) Inlet Pressure Tap
4) Outlet Pressure Tap
Ignitor
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
®
dealer for further
4
5
6
LRI4E / HRI4E Direct Vent Gas Insert
installation
3
2
1
|
17