PILOT ADJUSTMENT

Periodically check the pilot flames. Correct
flame pattern has two strong blue flames:
1 flowing around the flame sensor and 1
flowing across the burner (it does not have
to be touching the burner).
Burner
Flame Sensor
Pilot
Note: If you have an incorrect flame pattern,
contact your Regency
further instructions.
Incorrect flame pattern will have small,
probably yellow flames, not coming into
proper contact with the rear burner or flame
sensor.

HIGH ELEVATION

This unit is approved in Canada for altitude to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.
885 S.I.T. VALVE
DESCRIPTION
1) 6 Stage flame adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
P33CE-NG10 System Data
Burner Inlet Orifice Sizes:
Max. Input Rating
Min. Input Rating
Supply Pressure
Manifold Pressure
(High)
P33CE-LP10 System Data
Burner Inlet Orifice Sizes:
Ignitor
Max. Input Rating
Min. Input Rating
dealer for
®
Supply Pressure
Manifold Pressure
(High)
3
4
#44
20,000 Btu/h
14,000 Btu/h
min.5.0" w.c.
3.5"+/- 0.2"
w.c.
#55
19,500 Btu/h
15,500 Btu/h
min.11.0" w.c.
10"+/- 0.2"w.c.
2
1
7
installation
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1) Make sure the switch is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide flat
screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4) Light the pilot by turning the switch to "ON"
position.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6) When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not
over tighten.
4
3
2
1
5
6
P33CE-10 Direct Vent Gas Fireplace
|
35
7
|