AIR SHUTTER ADJUSTMENT

Air Shutters are required to increase or decrease the amount of air that is
mixed with the fuel before combustion. This will have an affect on how well
the fuel combusts and how the lame appears physically.
Low primary air will leave a taller, yellower lame while higher primary air will
leave a lower, bluer lame.
This setting is largely for appearance, however, not enough primary air may
lead to carboning, sooting or a lame that reaches the top of the irebox.
Situations that may require more primary air are; units that are burning
propane, units installed at higher elevations or units that are run on high
most of the time.
The LRI4E / HRI4E are equipped with an air shutter that is accessible from
outside the irebox and can be adjusted during operation.
Aeration adjustments should only be made after the unit has been on for 30
minutes to 1 hour.
Slide the Air Shutter Lever towards you to increase the primary air setting.
Slide the Air Shutter away from you to decrease the primary air setting.
Below you will see a chart showing the minimum primary air settings.
These are set from the factory, but due to fuel conversions or installation
conditions, the air setting may need to be adjusted.
Unit
LRI4E
LRI4E
HRI4E
HRI4E
HRI4E w/optional
driftwood logs
CAUTION: Carbon will be produced if air shutter is closed too much.
Note: any damage due to carboning resulting from improperly setting
the aeration controls is NOT covered under warranty.
Note: Aeration Adjustment should only be performed by an authorized
Regency Installer at the time of installation or service.
Note: The HRI4E with optional driftwood logs is only approved for use
with NG. This is not approved when using propane.
First Fire & Aeration
16 |
LRI4E / HRI4E Direct Vent Gas Insert
Fuel Type
Min. Air Setting
NG
3/16" (5mm)
LP
1/4" (6mm)
NG
3/16" (5mm)
LP
1/4" (6mm)
NG
Fully Open
Air Shutter
Air Shutter Lever
Firebox cut-away
to show location
of the Air Shutter
1) Slide the Air Shutter Lever towards you to increase the primary air set-
ting.
2) Slide the Air Shutter away from you to decrease the primary air setting.
Below you will see a chart showing the minimum primary air settings.
Close
Unit Front
Push to close - Pull to open
Burner Mounting
Bracket
Gas Orifice
Open