P36-NG10 System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #37
Max. Input Rating: 30,000 Btu/h
Min. Input Rating: 15,500 Btu/h
Supply Pressure:
min.5.0" w.c.
Manifold Pressure
(High):
3.8"+/- 0.2"w.c.
Electrical: 120 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fibre, 7 per set.
Vent System: Simpson Dura-Vent Direct
Vent System or Regency Direct Vent System (Flex)
P36-LP10 System Data
For 0 to 2000 feet altitude
Burner Inlet Orifice Sizes: #52
Max. Input Rating:
Btu/h
Min. Input Rating: 15,000 Btu/h
For 2000 to 4500 feet altitude
Burner Inlet Orifice Sizes: #53
Max. Input Rating 25,000 Btu/h
Min. Input Rating 12,600 Btu/h
For 0 to 4500 feet Altitude:
Supply Pressure
min.12.0" w.c.
Manifold Pressure
(High)
11"+/- 0.2" w.c.
Electrical: 120 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fibre, 7 per set.
Vent System: Simpson Dura-Vent Direct Vent
System or RegencyDirect Vent System (Flex)
HIGH ELEVATION
This unit is approved in Canada for altitude 0 to
4500 ft. (CSA 2.17) with the orifice supplied.
3 0 , 0 0 0
GAS LINE
INSTALLATION
The gas line is brought through the right of the
appliance. The gas valve is situated on the right
hand side of the unit and the gas inlet is on the
right hand side of the valve.
The gas line connection may be made of rigid pipe,
copper pipe or an approved flex connector. (If you
are using rigid pipe, ensure that the valve can be
removed for servicing.) Since some municipalities
have additional local codes it is always best to
consult with your local authorities and the CSA
B149.1 installation code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only
approved fittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and flex connectors are
usually considered to meet this requirement.
Important: Always check for gas leaks with a
soap and water solution or gas leak detector.
Do not use open flame for leak testing.
P36-10 Zero Clearance Direct Vent Gas Fireplace |
installation
|
43