4. Electrical installation
All types of three-phase asynchronous stand-
ard motors can be connected to the frequency
converter. Normally, small motors are star-
connected (230/400 V, D/Y). Large motors are
delta-connected (400/690 V, D/Y). Refer to
the motor name plate for correct connection
mode and voltage.
4
No.
No.
Table 4.6: 3 and 6 cable motor connection.

4.1.10. Motor wiring overview

Enclosure:
Motor size:
200-240 V
380-480 V
525-600 V
Goto:
Table 4.7: Motor wiring table.
30
NB!
In motors without phase insulation paper or other insulation reinforcement suitable
for operation with voltage supply (such as a frequency converter), fit an Sine-wave
filter on the output of the frequency converter. (Motors that comply with IEC
60034-17 do not require an Sine-wave filter).
96
97
98
Motor voltage 0-100% of mains voltage.
U
V
W
3 cables out of motor
U1
V1
W1
6 cables out of motor, Delta-connected
W2
U2
V2
U1
V1
W1
6 cables out of motor, Star-connected
U2, V2, W2 to be interconnected separately
(optional terminal block)
99
Earth connection
PE
A2
A3
(IP 20/IP
(IP 20/IP
(IP 55/IP
21)
21)
1.1-3.0
3.7
1.1-3.7
kW
kW
1.1-4.0
5.5-7.5
1.1-7.5
kW
kW
2.2-4.0
5.5-7.5
kW
kW
4.1.11
4.1.12
MG.11.A4.02 - 09.10.06. VLT
®
VLT
HVAC Drive Operating Instructions
Illustration 4.10: Terminals for motor connection
A5
B1
B2
(IP 21/IP
(IP 21/IP
66)
55/
55/
IP 66)
IP 66)
5.5-11
15
kW
kW
kW
11-18.5
22-30
kW
kW
kW
4.1.13
®
is a registered Danfoss trademark
C1
C2
(IP 21/IP
(IP 21/IP
55/
55/
IP 66)
IP 66)
18.5-30
37-45
kW
kW
37-55
75-90
kW
kW
4.1.14