*The display showing depends on choices made in parameter 0-02 and 0-03. The default setting
of parameters 0-02 and 0-03 depends on which region of the world the frequency converter is
supplied to but can be re-programmed as required.
No Operation
If
enable start.
Coast Inverse
If
essary to enable start.
Select
Select
graphs.
Only display parameters selected in par. 0-20 and par. 0-24 can be viewed. It is possible to store
up to 120 samples in the memory for later reference.
0-01
Value:
English (English)
1-20
Value:
0.09 - 500 kW
Function:
Enter the nominal motor power in kW accord-
ing to the motor nameplate data. The default
value corresponds to the nominal rated output
of the unit.
This parameter cannot be adjusted while the
motor is running.
1-21
Value:
1.5 - 55 HP
Function:
Enter the nominal motor power in HP accord-
ing to the motor nameplate data. The default
value corresponds to the nominal rated output
of the unit.
This parameter cannot be adjusted while the
motor is running.
is selected in terminal 27 no connection to +24 V on terminal 27 is necessary to
(factory default value) is selected in Terminal 27, a connection to +24V is nec-
Changes made
to get information about:
the last 10 changes. Use the up/down navigation keys to scroll between the last 10
changed parameters.
the changes made since default setting.
Loggings
to get information about the display line read-outs. The information is shown as
Language
Motor power parameter
Size related
Motor Power [HP]
Size related
MG.11.A4.02 - 09.10.06. VLT
6. How to programme the frequency converter
1-22
Motor Voltage
Value:
10 - 1000 V
[0]
Function:
Enter the nominal motor voltage according to
the motor nameplate data. The default value
corresponds to the nominal rated output of
the unit.
This parameter cannot be adjusted while the
motor is running.
1-23
Motor Frequency
Value:
20 - 1000 Hz
Function:
Select the motor frequency value from the
motor nameplate data. For 87 Hz operation
with 230/400 V motors, set the nameplate da-
ta for 230 V/50 Hz. Adapt par. 4-13
Speed High Limit [RPM)
mum Reference
This parameter cannot be adjusted while the
motor is running.
®
is a registered Danfoss trademark
Size related
Size related
Motor
Maxi-
and par. 3-03
to the 87 Hz application.
6
57