6. How to programme the frequency converter
Cascade Pump1
Cascade Pump2
Cascade Pump3
Fire Mode Active
Fire Mode Coast
Fire Mode Was Active
Alarm, Trip Locked
Bypass Mode Active
Function:
Select options to define the function of the re-
lays.
The selection of each mechanical relay is re-
alised in an array parameter.
6
6-00
Value:
1 - 99 s
Function:
Enter the Live Zero Time-out time period. Live
Zero Time-out Time is active for analog in-
puts, i.e. terminal 53 or terminal 54, allocated
to current and used as reference or feedback
sources. If the reference signal value associ-
ated with the selected current input falls be-
low 50% of the value set in par. 6-10, par.
6-12, par. 6-20 or par. 6-22 for a time period
longer than the time set in par. 6-00, the func-
tion selected in par. 6-01 will be activated.
6-01
Value:
Off
Freeze output
Stop
Jogging
Max. speed
Stop and trip
Function:
Select the time-out function. The function set
in par. 6-01 will be activated if the input signal
on terminal 53 or 54 is below 50% of the value
in par. 6-10, par. 6-12, par. 6-20 or par. 6-22
for a time period defined in par. 6-00. If sev-
eral time-outs occur simultaneously, the fre-
74
[211]
[212]
[213]
[220]
[221]
[222]
[223]
[224]
Live Zero Timeout Time
Live Zero Timeout Function
MG.11.A4.02 - 09.10.06. VLT
®
VLT
quency converter prioritises the time-out
functions as follows:
1.
Par. 6-01
tion
2.
Par. 8-04
Function
The output frequency of the frequency con-
verter can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to jog speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subse-
quent trip
If you select set-up 1-4, par. 0-10,
up
, must be set to
Multi Set-up
This parameter cannot be adjusted while the
motor is running.
10s
6-10
Terminal 53 Low Voltage
[0]
Value:
[1]
0.00 - par. 6-11
[2]
Function:
Enter the low voltage value. This analog input
[3]
scaling value should correspond to the low
[4]
reference/feedback value set in par. 6-14.
[5]
6-11
Terminal 53 High Voltage
Value:
Par. 6-10 to 10.0 V
®
is a registered Danfoss trademark
HVAC Drive Operating Instructions
Live Zero Time-out Func-
Control-word Time-out
Active Set-
, [9].
0.07V
10.0V