VLT
HVAC Drive Operating Instructions
4. Electrical installation
4.1.11. Motor connection for A2 and A3
Follow these drawings step by step for connecting the motor to the frequency converter.
4
Illustration 4.11: First terminate the motor earth, then place motor U, V and W wires in plug and tighten.
Illustration 4.12: Mount cable clamp to ensure 360 degree connection between chassis and screen, note the
outer insulation of the motor cable is removed under the clamp.
31
MG.11.A4.02 - 09.10.06. VLT
®
is a registered Danfoss trademark