Advertisement

®
VLT
HVAC Drive Operating Instructions

4. Electrical installation

4.1. How to connect

4.1.1. Cables General
Details of terminal tightening torques.
Enclo-
sure
A2
A3
A5
B1
B2
C1
C2
Table 4.1: Tightening of terminals.
4.1.2. Fuses
Branch circuit protection
In order to protect the installation against electrical and fire hazard, all branch circuits in an in-
stallation, switch gear, machines etc., must be shortcircuit and overcurrent protected according
to the national/international regulations.
Short circuit protection
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard.
Danfoss recommends using the fuses mentioned in tables 4.3 and 4.4 to protect service personnel
or other equipment in case of an internal failure in the unit. The frequency converter provides full
short circuit protection in case of a short-circuit on the motor output.
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation.
Over current protection must always be carried out according to national regulations. The fre-
quency converter is equipped with an internal over current protection that can be used for
upstream overload protection (UL-applications excluded). See VLT
Guide, par. 4-18. Fuses must be designed for protection in a circuit capable of supplying a maxi-
mum of 100,000 A
NB!
Cables General
Always comply with national and local regulations on cable cross-sections.
Power (kW)
200-24
380-48
525-60
0 V
0 V
0 V
1.1 - 3.0 1.1 - 4.0 1.1 - 4.0
3.7
5.5 - 7.5 5.5 - 7.5
1.1 - 3.7 1.1 - 7.5 1.1 - 7.5
11 -
5.5 - 11
-
18.5
-
22
-
15
30
-
18.5 -
37 - 55
-
30
37
75
-
45
90
-
(symmetrical), 500 V/600 V maximum.
rms
MG.11.A4.02 - 09.10.06. VLT
®
is a registered Danfoss trademark
Torque (Nm)
DC con-
Line
Motor
Brake
nection
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.5
2.5
2.5
3.7
4.5
4.5
3.7
10
10
10
14
14
14
24
24
14
®
4. Electrical installation
Earth
Relay
1.8
3
0.6
1.8
3
0.6
1.8
3
0.6
1.5
3
0.6
3.7
3
0.6
3.7
3
0.6
10
3
0.6
14
3
0.6
14
3
0.6
HVAC Drive Programming