Danfoss VLT HVAC Operating Instructions Manual page 87

Hide thumbs Also See for VLT HVAC:
Table of Contents

Advertisement

®
VLT
HVAC Drive Operating Instructions
4-56
Value:
-999999.999 to
+999999.999
Function:
Enter the lower feedback limit. When the
feedback falls below this limit, the display
reads Feedb Low. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29 and on relay output 01 or
02.
NB!
When you carry out manual initialisation, you also reset serial communication, RFI
filter settings (par. 14-50) and fault log settings.
Removes parameters selected in
NB!
After initialization and power cycling, the display will not show any information until
after a couple of minutes.
Warning Feedback Low
-999999.999
MG.11.A4.02 - 09.10.06. VLT
®
is a registered Danfoss trademark
6. How to programme the frequency converter
Personal Menu
.
6
87