Commissioning

6.3 User-specific commissioning

6.3
User-specific commissioning
If values are required that differ from the defined parameters in the Quick Start menu or in
the factory settings of the 3RW44, please proceed as follows:
Under the "Settings" menu item, select (refer to chapter Settings main menu item (Page 59)).
1. Selecting the parameter set
2. Set motor data
3. Set startup mode and parameters
4. Set coasting method and parameters
5. Set inputs and outputs
6. Check motor protection settings
7. Saving settings
58
NOTICE
The setting is buffered in a Flash EPROM memory as soon as you change a setting in
the menu and execute it using the "OK" button. It is then active in the soft starter as from
this moment onwards. When the control supply voltage is switched off, this value will be
canceled and the previous value restored. To permanently save the settings made in the
soft starter, you must save the data as described in chapter Settings main menu item
(Page 59) and chapter Saving options (Page 102).
Manual, 03/2017, NEB535219502000/RS-AB/008
3RW44 soft starters