PROFIBUS DP communication module
9.6 PROFIBUS DP commissioning using the GSD file in STEP 7 (example)
Step
6
7
8
9
10
11
12
Note
During parameterization with the GSD file, it is possible to select values that are dependent
on each other, but are not permissible in combination. The respective parameter is reported
as an "Incorrect parameter value" in data set 92.
166
Description
In HW Config, call up the Extras > Install new GSD file menu command, and integrate
the GSD file of the soft starter into the configuration tool of the DP master used. For the
CPU315-2 used in the example, you can optionally install
the German GSD file SIEM80DE.GSG,
the English GSD file SIEM80DE.GSE,
the French GSD file SIEM80DE.GSF,
the Spanish GSD file SIEM80DE.GSS,
the Italian GSD file SIEM80DE.GSI
in the STEP 7 SIMATIC Manager.
Generate the PROFIBUS DP subnet.
Add the soft starter from the hardware catalog to the PROFIBUS under PROFIBUS DP >
Additional field devices > Switching devices > Motor starters > Direct soft starters >
SIRIUS 3RW44.
Set the station address for the soft starter to 3 (or higher).
Drag a module from the selection list of the drop-down menu to slot 1 of the SIRIUS
3RW44:
Depending on the structure
*)
Double-click to open the "Properties DP slave" dialog.
Click on "Parameterize". Set the parameters, **), e.g.
:
Rated operational current
:
Click on OK. This completes the configuration.
Save the configuration.
Manual, 03/2017, NEB535219502000/RS-AB/008
3RW44 soft starters