Switching On For The First Time; Recommended Procedure For Commissioning 3Rw44 - Siemens 3RW44 Manual

Industrial control soft starters
Hide thumbs Also See for 3RW44:
Table of Contents

Advertisement

Commissioning

6.2 Switching on for the first time

6.2
Switching on for the first time
Before switching the device on for the first time, verify that the main/control side is wired
properly. Make sure that the line and control voltages comply with the device-specific
requirements (refer to chapter Technical data (Page 253)).
6.2.1

Recommended procedure for commissioning 3RW44

Suggested
Startup parameters
setting
Startup mode: voltage ramp and current limiting (U+ current
limiting)
Starting
voltage %
Application
Conveyor
70
belts
Roller
60
conveyors
Compressor
50
Small fans
30
Pump
30
Hydraulic
30
pumps
Stirrers
30
Centrifuges
30
Milling
30
machines
Large fans
30
Mills
50
Crushers
50
Circular
30
saws/band
saws
Note
This table provides example settings. They are intended for information purposes only and
are not binding. Set values depend on the application in question and must be optimized
during commissioning.
50
WARNING
Starting
Current limiting
time s
value
10
Deactivated
10
Deactivated
10
4 x I
e
10
4 x I
e
10
4 x I
e
10
4 x I
e
30
4 x I
e
30
4 x I
e
30
4 x I
e
60
4 x I
e
60
4 x I
e
60
4 x I
e
60
4 x I
e
Stopping parameters
Coasting method
Breakaway pulse
Deactivated (0 ms)
Torque control
Deactivated (0 ms)
Torque control
Deactivated (0 ms)
Coasting down
Deactivated (0 ms)
Coasting down
Deactivated (0 ms)
Pump stop
Deactivated (0 ms)
Coasting down
Deactivated (0 ms)
Coasting down
Deactivated (0 ms)
Coasting down
Deactivated (0 ms)
Coasting down
Deactivated (0 ms)
Coasting down
80 %/300 ms
Coasting down
80 %/300 ms
Coasting down
Deactivated (0 ms)
Coasting down
Manual, 03/2017, NEB535219502000/RS-AB/008
Parameters
Coast-
Stopping
down
torque %
time s
10
10
10
10
X
X
X
X
10
10
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
3RW44 soft starters

Advertisement

Table of Contents
loading

Table of Contents