3.2 Startup class
3.2.1
Application examples for normal starting (CLASS 10)
Normal starting CLASS 10 (up to 20 s with 350 % I
The soft starter rating can be selected to be as high as the rating of the motor implemented.
Application
Conveyor belts
Starting parameters
Voltage ramp
and current
limiting
70
Starting
•
voltage %
10
Starting
•
time s
Deactivated
Current
•
limiting
value
Torque ramp
60
Starting
•
torque
150
End torque
•
10
Starting
•
time
Breakaway
Deactivated
pulse
(0 ms)
Coasting
Soft stop
method
22
Roller
Compressor
conveyors
60
50
10
10
Deactivated
4 x I
M
50
40
150
150
10
10
Deactivated
Deactivated
(0 ms)
(0 ms)
Soft stop
Coasting down
)
n motor
Small fans
Pump
30
30
10
10
4 x I
Deactivated
M
20
10
150
150
10
10
Deactivated
Deactivated
(0 ms)
(0 ms)
Coasting down
Pump stop
Manual, 03/2017, NEB535219502000/RS-AB/008
Hydraulic
pumps
30
10
Deactivated
10
150
10
Deactivated
(0 ms)
Coasting down
3RW44 soft starters