Siemens 3RW44 Manual page 179

Industrial control soft starters
Hide thumbs Also See for 3RW44:
Table of Contents

Advertisement

Note
Channel-related diagnostics is always updated up to the current diagnostics message in the
diagnostics message frame. Subsequent, older diagnostics messages are not deleted.
Remedy: Evaluate the valid, current length of the diagnostics message frame:
• STEP 7 from the parameter RET_VAL of SFC 13.
Fault types
The diagnostics alarm is signaled on channel 0.
Table 9- 14
Fault types
Fault
Fault type
No.
F1
00001:
Short-circuit
F4
00100:
Overload
F5
00101:
Overtemperature
F6
00110:
Wire break
F7
00111:
Maximum limit value
exceeded
F8
01000:
Minimum limit value
undershot
F9
01001:
Error
F16
10000:
Parameterization error
F17
10001:
No sensor or load voltage
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
Meaning/cause
Short-circuit of the
temperature sensor
Overload of the temperature
sensor
Overload of the thermal motor
model
Overload of the contact block
Wire break of the temperature
sensor
I
limit value overshot
e
I
limit value undershot
e
Internal error/device error
Contact block defective
Invalid parameter value
Electronics supply voltage too
low
No contact block supply
voltage
No supply voltage
PROFIBUS DP communication module
9.9 Diagnosis with STEP 7
Delete alarm bit/acknowledgement
Alarm bit is automatically deleted when the
cause of the fault has been removed and
acknowledged with "trip reset".
Alarm bit is updated continually.
Alarm bit is automatically deleted when the
cause of the fault has been removed and
acknowledged with "trip reset".
Alarm bit is updated continually.
Alarm bit can be deleted when the cause of
the error has been eliminated by
Switching the supply voltage On and Off
"Restart" command if possible
Alarm bit is always deleted when
acknowledged with "trip reset".
Alarm bit is deleted when the cause of
tripping has been eliminated or automatically
acknowledged.
179