ID No. Byte
Meaning
Bit
163
96
Output 1 - action
164
97
Output 2 - action (see Output 1 -
action)
165
98
Output 3 - action (see Output 1 -
action)
166
99
Output 4 - action
100...111
Reserved = 0
116
112
Breakaway time
117
113
Breakaway voltage
169
114...115
Maximum starting time
170
116...117
Starting time
171
118...119
Coast-down time
172
120
Starting torque
118
121
Limiting torque
173
122
Stopping torque
123
Reserved = 0
124
Reserved = 0
119
125
Motor thermal capacity
126...129
Reserved = 0
178
130
Dynamic braking torque
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
PROFIBUS DP communication module
Only in
Value range/[coding]
data set
131
X
No action (default) [0]
Control source PIO DO 1.0 output 1 [1]
Control source PAA-DO 1.1 output 2
[2]
Control source input 1 [6]
Control source input 2 [7]
Control source input 3 [8]
Control source input 4 [9]
Run-up [10]
Operation/bypass [11]
Coasting down [12]
ON time motor [13]
Control command motor ON [14]
Fan [15]
DC brake contactor [16]
Device ON [18]
Group warning [31]
Group fault [32]
Bus fault [33]
Device fault [34]
Ready to start ON for motor [38]
X
X
0 ... 2 s [0 ... 200]
40 ... 100 % [8 ... 20]
0 ... 1 000 s [0 ... 10 000]
0 ... 360 s [0 ... 3 600]
0 ... 360 s [0 ... 3 600]
10 ... 100 % [2 ... 20]
20 ... 200 % [4 ... 40]
10 ... 100 % [2 ... 20]
1 ... 100 % [1 ... 100]
20 ... 100 % [4 ... 20]
9.12 Data sets (BS)
Factor
0.01 s
5 %
0.1 s
0.1 s
0.1 s
5 %
5 %
5 %
1 %
5 %
211