Master Profibus Address; Manufacturer Id; Id-Related Diagnostics - Siemens 3RW44 Manual

Industrial control soft starters
Hide thumbs Also See for 3RW44:
Table of Contents

Advertisement

PROFIBUS DP communication module
9.9 Diagnosis with STEP 7
9.9.5

Master PROFIBUS address

The master PROFIBUS address diagnostics byte contains the station address of the DP
master:
● that has parameterized the DP slave and
● has read and write access to the DP slave.
The master PROFIBUS address is stored in byte 3 of the slave diagnostics.
9.9.6

Manufacturer ID

Definition
The manufacturer's ID contains a code specifying the DP slave type.
Table 9- 13
Byte 4
80
H
9.9.7

ID-related diagnostics

Definition
Identifier-related diagnostic data indicates whether soft starters are faulty or not. Identifier-
related diagnostics begins at byte 6 and is 2 bytes long.
ID-related diagnostics
Identifier-related diagnostics for soft starters is structured as follows:
Figure 9-5
176
Structure of the manufacturer ID
Byte 5
DE
H
Configuration of identifier-related diagnostics
Manufacturer ID for
Soft starter
Manual, 03/2017, NEB535219502000/RS-AB/008
3RW44 soft starters