PROFIBUS DP communication module
9.12 Data sets (BS)
ID No. Byte
Meaning
Bit
35
52...53
Substitute value
54...55
Reserved = 0
56
Reserved = 0
0...5
36
56
Group diagnostics
6
34
56
Response to CPU/master STOP
7
57...75
Reserved = 0
26
76
Input 1 - action
28
77
Input 2 - (see Input 1 - action)
30
78
Input 3 - (see Input 1 - action)
32
79
Input 4 - (see Input 1 - action)
80...95
Reserved = 0
210
Only in
Value range/[coding]
data set
131
X
The "Substitute value" parameter is only
relevant if the "Response to CPU/master
STOP" parameter has been set to "Switch
substitute value", see Process data and
process images (Page 170)
Motor CW 52 [0]
Motor CCW (only if 52 [6] active) 52 [1]
Trip reset 52 [3]
Emergency start 52 [4]
Slow speed 52 [6]
Output 1 53 [0]
Output 2 53 [1]
Parameter set bit 0 53 [2]
Parameter set bit 1 53 [3]
X
Disable [0]
Enable [1]
X
Switch substitute value [0]
Hold last value [1]
X
No action (default) [0]
Manual mode local [6]
Emergency start [7]
Slow speed [10]
Quick stop [11]
Trip reset [12]
Motor CW with PS1 [16]
Motor CCW with PS1 [17]
Motor CW with PS2 [18]
Motor CCW with PS2 [19]
Motor CW with PS3 [20]
Motor CCW with PS3 [21]
X
X
X
Manual, 03/2017, NEB535219502000/RS-AB/008
Factor
3RW44 soft starters