Installation And Getting Started - Siemens CPU 948 Programming Manual

Simatic s5 s5-155u
Table of Contents

Advertisement

11.5.3
Installation and Getting
Started
The CP 143 is used
exclusively for
PG Functions
Step
1
Set the interface number (SSNR) on the CP 143 (jumpers):
Select the SSNR according to the existing hardware configuration as shown below.
Keep in mind the explanations in Further Reading /6/.
Possible hardware configuration
1 x CPU 948, 1 x CP 143
1 x CPU 948, 2 x CP 143
2 x CPU 948, 1 x CP 143
3 x CPU 948, 2 x CP 143
4 x CPU 948, 2 x CP 143
2
Insert the CP 143 in the S5-155U (power supply to the PLC must be off).
3
Connect the PG to the PG interface of the CP 143 and load the COM program.
4
Set the interface number selected in step 1 in the SYSID of the CP 143 using COM 143
and set the Ethernet address.
CPU 948 Programming Guide
C79000-G8576-C848-04
During installation, remember the following alternatives.
If the CP 143 is used exclusively for PG functions via the S5 bus, no
further parameters other than the SINEC H1 parameters must be set.
After POWER UP, the PG functions are always available on CPU 948
via the S5 bus without the CP 143 previously being synchronized with
the HDB SYNCHRON (FB 125). The mode selector on the CPU
must, however, be set to RUN.
An "empty" CPU 948 can be started up via the S5 bus without an
OVERALL RESET.
After POWER UP, the CPU 948 automatically synchronizes the pages
assigned to it on the CP 143 for PG functions via the S5 bus.
The following steps are necessary for starting up:
Action
PG Functions via the S5 Bus
Corresponding SSNR on the CP 143
232
232 on 1st CP, 236 on 2nd CP
232
232 on 1st CP, 236 on 2nd CP
232 on 1st CP, 236 on 2nd CP
11 - 31