OB 153: Set/Read Time for Delayed Interrupt
Stop delay time (cancel job)
STEP 5 operations for calling OB 153:
:
:
:L
KF +2
:
:JU
OB 153
:
:
Read out remaining time of a delay job:
STEP 5 operations for calling OB 153:
:
:
:L
KF +3
:
:JU
OB 153
:
:
:
:
6 - 52
Value for ACCU-1-L: function no. = 2 for
"stop delay time"
Call OB 153
Value for ACCU-1-L: function no. = 3 for
"read out remaining time"
Call OB 153
ACCU-1-L contains the time the delay job still
has to run.