Siemens CPU 948 Programming Manual page 299

Simatic s5 s5-155u
Table of Contents

Advertisement

Result
Possible errors
CPU 948 Programming Guide
C79000-G8576-C848-04
2b) ACCU-1-L
Number of the 1st data field word,
possible values (depending on the
address area type:
DB, DX:
F flags:
S flags
After correctly processing OB 182: RLO, condition code bits OR,
ERAB and OS = 0.
If an error occurs, an error ID is entered in ACCU 1 (see table below).
Table 6-18
Error IDs of OB 182 in ACCU-1-L
ACCU-1-L Meaning
B601H
Data block not loaded
B60FH
Multiple block call
B611H
Incorrect content in the data field
B612H
Address area type illegal
B613H
Data block no. illegal
B621H
"Number of the 1st data field word" illegal
B622H
"Source data block type" illegal
B623H
"Source data block no." illegal
B624H
"No. of the 1st data word to be transmitted in source
DB" illegal
B625H
Length of the source data block in the block header
< 5 words
B626H
"Destination data block type" illegal
B627H
"Destination data block no." illegal
B628H
"No. of 1st data word to written in destination
DB" illegal
B629H
Length of the destination block in block header < 5
B62AH
words
"Number of data words to be transmitted" illegal
B62BH
(= 0 or > 4091)
B62CH
Source data block too short
Destination data block too short
OB 182: Copy Data Area
0 to 2038
0 to 246
(= No. of flag byte 'x ')
0 to 4086
(= No. of flag byte 'x ')
6 - 61