CONDITION CODE
CAUSE OF INTERR.
CPU 948 Programming Guide
C79000-G8576-C848-04
see Section 3.5
The following abbreviations (ISTACK IDs) indicate the most important
causes of interruptions.
Table 5-6
ISTACK IDs CAUSE OF INTERRUPTION
CAUSE OF INTERR.
ISTACK
Meaning (called error OB)
ID
KB
Called block not loaded (OB 19)
KDB
Opened data block not loaded (OB 19)
TRAF
Load or transfer error (OB 32)
SUF
Substitution error (OB 27):
Processed STEP 5 operation cannot be
substituted
STUEB
Block stack overflow:
Nesting depth too great; required action:
COLD RESTART
STUEU
Interrupt stack overflow:
Nesting depth too great; required action:
POWER DOWN, POWER UP,
then COLD RESTART
NAU
Power failure in the central controller
QVZ
Timeout (OB 23/OB 24/OB 28/OB 29)
ADF
Addressing error for digital inputs and outputs with
process image (OB 25)
PARE
Parity error (OB 30)
ZYK
Cycle monitoring time exceeded (OB 26)
STOP
STOP mode caused by setting the mode selector to the
STOP position
STS
STOP mode caused by STEP 5 operation 'STS' (after
executing an operation)
Control Bits and Interrupt Stack
5 - 17