DX 0/DB1 errors
CPU 948 Programming Guide
C79000-G8576-C848-04
Error
Parameter
number
type
Table 8-9 continued:
1DH
08H
AUTOMATIC WARM RESTART not
possible; COLD RESTART required
1EH
00H
Illegal start-up type
1FH
01H
Load/transfer error during block transfer
operation (incorrect memory area boundaries
with TNW, TXB, TXW)
20H
09H
Illegal length for G DB/GX DX
21H
09H
DB/DX already exists for G DB/GX DX
22H
09H
Memory space insufficient for G DB/GX DX
23H
05H
Masked system interrupt is coming through
24H
00H
Block function (compress, transfer, input)
required in STOP, COLD RESTART
25H
00H
Battery failure; no start-up possible
26H
00H
Change from single to multiprocessor
operation prevents a WARM RESTART
27H
01H
STOP caused by STP operation
28H
01H
Continuous ready signal (I/O module defect))
29H
08H
Error in DB 0 struct. after OVERALL RESET
Table 8-10
RS 75: Errors in DX 0 or DB 1
Error
Parameter
number
type
30H
00H
No DX 0 in multiprocessing
32H
00H
Proc. int. and sys. int. selected simultaneously
33H
00H
Interrupts and mode incompatible
34H
06H
Invalid DX 0 header
35H
07H
Error in DX 0 block ID
36H
07H
Error in DX 0 parameter
38H
06H
No DB 1 in multiprocessing
39H
06H
Invalid DB 1 header
3AH
07H
DB 1 ID set more than once
3BH
07H
DB 1 byte offset without ID
Bit Assignment of the System Data Words
Meaning
Meaning
Errors in DX 0
Errors in DB 1