Table 12.1 Main Circuit Cable
Size (mm2 ) '"te
Terminal Name and Screw Size
Inverter
Mod
Rated
600V Class
CIMR-VM::
c&
y;:?
Fke-registant
600V Class
Inverter Terminal
Motor
Crosslinked
Rubbet'-insulated
Terminal
Polyethylene Cable
Cabtyre 400V Cable
Input
output
,
200V
23P7
22
3.5
2.0
3.5
M5
M5
M4
25P5
33
5.5
3.5
5.5
MS
M5
M5
27P5
45
8.0
5.5
8.0
M5
M5
M5
2011
66
14.0
14.0
14.0
M8
M8
M8
2015
90
30.0
22.0
22.0
M8
M8
M8
2018
111
38.0
.22.0
28.0
M8
M8
M8
2022
132
50.0
30.0
50.0
M8
M8
M8
2030
180
50.0
M8
M8
M8
400V
43P7
11
2.0
2.0
2.0
M5
M5
M4
45P5
16
2.0
2.0
2.0
M5
M5
M5
47P5
22
3.5
2.0
3.5
M5
M5
M5
4011
33
5.5
3.5
5.5
M8
M8
M8
4015
45
8.0
5.5
8.0
M8
M8
M8
4018
55
14.0
8.0
14.0
M8
M8
M8
4022
66
14.0
14.0
22.0
M8
M8
M8
4030
90
30.0
22.0
30.0
M8
M8
M8
Terminal Name
R, s,
u, v,
u, v,
T, E
W, E
W, E
Note: Cable size isselected
atambient temperature30~
when built with 3-core l-thread in the air.
The maxium allowable temperature of the conductor is 60~ for IV, VV and CT cables, and 110"C
for 600V fire-resistant crosslinked polyethylene cables.
Precautions on Cable Selection at High Ambient Temperature —>
When ambient temperature exceeds 30C, thecable allowable cument is reduced. Select thecable size in
accordance with the technical materials of the cable manufacturer based on rated current.
Table 12.2 Cooling Fan Motor Cable
Terminal Name and Screw Size
Inverter
Cable
Inverter Terminal
Control Power
Cooling Fan
Motor Terminal
Input
output
200V
600V Class polyvinyl insulated wire,
400V
Size 2mmZ
M4
M4
M4