Access To The Connection Terminal - REMEHA CALORA TOWER GAS 15S EX Installation And Service Manual

Floor-standing high efficiency gas boiler
Table of Contents

Advertisement

5. Installation
1
36
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
4 The instructions on the circuit diagrams provided with the
appliance.
4 The manufacturer's instructions.
CAUTION
Separate the sensor cables from the 230 V cables.
4
All connections are made with the terminal boxes designed for that
purpose on the back of the boiler's command board. The connection
cables are threaded into the boiler through the space provided
between the top panel and the upper rear panel. These cables will be
fixed on to the control panel with cable clips (supplied in a separate
bag).
Power the appliance via a circuit which includes a remote omnipolar
switch with a gap of more than 3 mm.
The available output per outlet is 450 W (2 A, with cos j = 0.7) and
the inrush current must be lower than 16 A. If the load exceeds either
of these values, the control must be relayed using a contactor that
must not be installed in the control panel under any circumstances.
CAUTION
Failure to comply with these instructions could lead to
interference and control unit malfunctioning or even
damage to the electronic circuitry.
5.8.3.

Access to the connection terminal

1. Open and remove the control panel door.
C003099-D
Outside the boiler: Use 2 pipes or cable guides at
least 20 cm apart.
CALORA TOWER GAS 35S EX
22/04/2016 - 300026141-001-07